Product Description
TC-ZJH5008 loop extender is powered by DC24V, and the input and output of bus signals are electrically isolated, which can enhance the anti-interference ability of the whole fire alarm system and has the function of extending the communication distance of the detector bus.
II. Characteristics
1. Built-in isolated power supply with strong interference capability;
2. And the bus and the DC24V power line are non-polar connected;
3. Raise bus voltage and extend bus communication distance;
4. With output short circuit detection function;
5. Up to 255 devices can be attached;
6. Plug-in structure, convenient and reliable installation;
Technical Specifications
1. Operating voltage:
Rated working voltage of signal bus: DC24V range: DC17V~DC28V
Power supply rated working voltage: DC24V range: DC18V~DC36V
2. Operating current:
Monitoring current ≤0.3mA
3. Output capacity: 400mA
4. Load capacity and compatibility: 1 ~ 255 bus devices can be connected, compatible with all detector bus devices.
5. Bus extension distance: 1000m
6. Indicator: There is an answer indicator (red). The indicator does not light when it is normal, and the indicator flashes when the detector answers; With an overload indicator (yellow), the indicator is not on when it is normal, and it is always on when the loop extender output is short-circuited.
7. Environment:
pressure: 86 kPa ~ 106 kPa
Temperature: 0℃ ~+55℃
Relative humidity ≤95%, no condensation.
8. Dimensions: 86mm×86mm×40mm (with cover)
9. Material and color: ABS, porcelain white
10. Weight: about 147g (with cover)
11. Mounting hole distance: 60mm

© Copyright 2018~2025 by vedard.com