Small business fire security solution with conventional fire alarm systems. 2 wire smoke detector, 2 wire heat detector, gas sensor, manual call point, siren strobe all fire detection sensors for conventional fire alarm system.
2 zones, 4 zones or 6 zones Conventional fire alarm systems are used for restaurant, store, shop, family hotel for fire security.
Conventional fire alarm system can equip with fire extinguish panel gas fire extinguish and fire sounder lighter for evacuation.
Conventional Maintenance Switch For Gas Extinguisher System
This MAINTENANCE panel is a key switch, which disconnects actuation circuits in the system to prevent accidental discharge during maintenance operations.
Two “LEDS” indicate “SYSTEM ARMED” and “SYSTEM INACTIVE”. When the key is inserted and turned towards “SYSTEM INACTIVE”, the red LED illuminates and the green LED indicating “SYSTEM ARMED” turns off. The key can only be removed in the “SYSTEM ARMED” position.
This panel is also available with the key removable in both the “ARMED” and the “INACTIVE” positions.
The information is silk-screened on a two-gang stainless plate.
Switch rated at 5A 250VAC, the DC rating is 5A up to 30VDC.
LEDS rated at 10mA each for a total current draw of 20mA.
Video guidance to instruct how to install gas fire extinguishing fire alarm and fire automatic fighting system
Fire floor display and repeat panels have the following key features:
16 conventional repeater display zones.
Fire alarm output relay and 1 fault output relay .
Fire alarm output with 24VDC.
RS485 can be able to connect the other panel.
You can download the complete fire alarm system category and installation instruction manual fire alarm installation
Specifications
Power supply: 16VDC to 30VDC
Current of power: Standby current: ≤15mA, Alarm current: ≤75mA
Relay contact capacity: 2A@24VDC
Buzzer level: 80dB@1m.
Protection level: IP55
Communication mode:RS485 (Wires: RVSP type,1.0MM2 to 2.0MM2)
Dimension of enclosure: 200mm(W)*91mm(H)*45mm(D)
Material of enclosure:ABS, White
Weight: 350g.
Hole of enter wires: 1/2 inch(12mm)
Repeater status indication and button operation
FIRE ALARM Status: When a fire alarm occurs, the corresponding zone red LED flashing and the internal buzzer sounds. When “Silence” button pushed, the alarm zone LED lights steady and the buzzer silenced.
When another new fire alarm occurs, the new zone red LED flash and the buzzer sound again. In the fire alarm status, the fire alarm “FIRE OUT” relay active and output “NO, NC, C” relay contacts and 24vdc power output.
FAULT Status: When a fault event occurs, the corresponding zone’s yellow LED flashing and the internal buzzer sounds. When “Silence” button pushed, the fault zone LED lights steady and the buzzer silenced.
When another new fault event occurs, the new zone yellow LED flash and the buzzer sound again. In the fault alarm status, the fault alarm “FAULT OUT” relay active and output “NO, NC, C” relay contacts.
Normal status: When fire alarm panel’s fire or fault event restored, the fire alarm panel would send commands to let the repeater to the Normal Status.
RUN LED: The “RUN” LED would keep light steady when the power supply in normal status.
COMM. LED: The “COMM.” LED would flash once about three to five seconds in normal communication status.
SILENCE LED: In the fire or fault alarm status, press the “Silence” button the “SILENCE” LED would turn on .
TEST LAMP: In normal status, press “TEST” button would have a lamp test.
SILENCE SOUND: In fire or fault status, press “SILENCE” button would silence the alarm sound.
RESET: In the “SILENCE” status,press “RESET” button once the repeater would return to the Normal Status.