TCDZ516 Isolating Base, mainly applied in bus-based fire detection and alarm system, can isolate the short-circuit detector or wire out of the system to ensure the normal running of other devices. This device can provide bidirectional protection under low power consumption with the inspection method of hardware and software combination. It is applicable to bus-based fire detection and alarm systems of all types.
TCDZ 516 Isolating Base features:
1. share the address with the associating devices
2. the microprocessor is adopted to realize signal processing, and the digital signal is used to communicate with the fire alarm control panel, which works stably and reliably, and has a good ability to suppress electromagnetic interference.
3. electronically coding.
TCDZ 516 Isolating Base specification:
Working voltage: Voltage of signal bus: Bus 24V Range: DC16V~DC28V
Working current:
Vnom: 24V
ISO max: 750mA
ISO min: 280mA
ISC max: 31mA
ISC min: 12mA
IL max: 35mA
IS max: 900mA
IC max: 580mA
ZC max: 0.6Ω
Indicator light:yellow, extinguished in normal monitoring state, and always on during operation
Wire system: Polar two bus connection
Protection level: IP30
Use environment: Temperature: -10℃~+55℃
Relative humidity≤95%, non-condensing
Outline dimension: Dia.100mm, thickness:19mm
Housing material: ABS
Weight: about 76g
Distance between installation holes: 60mm
TC5109 Intelligent Fire Alarm Control Panel Core Functions: Fire Alarm Monitoring, Fault Detection & Indication, Device & Zone Management, Linkage Control, System Operation & Control, Communication & Networking, Display & Output.
Integral of fire monitoring, information transmission and fire protection safety management RS232 interface is switched to RS485 interface by internal interface board, thus to be connected with TC5000 series such as TC5109 automatic Fire Alarm Control Panel Display general layout, alarm plane figure and system graph with the functions of information display, duty management, evacuation indication, query, printing, etc Man-machine friendly, vivid and convenient operation. Model No.: TCCRT-5017B Voltage: AC220V(AC185V~AC242V), 50Hz+1Hz or AC110V (AC90V~AC120V),60Hz +1Hz Current: 300mA LED Screen: 19 inch Operating Environment: Temperature: 0°C~ +40°C; Relative Humidity:≤95% Interface: RS232, RS485, LAN/WAN Dimension (LxWxH): 482mmx 1 83mm x444mm Approval: CCCF, CE
$530.00Alarm location display panel fire floor screen
TCFS5089 TC brand LPCB approval professional intelligent addressable fire alarm system.
Model No.: TCFS5089
It is used to display the fire location and related information of a certain floor or fire zone, and at the same time send out an sounder strobe alarm signals to inform people in nearby areas.
* Display Fire Alarm position and information for certain floor or fire protection zone, give out audio and visual alarm signal to inform nearby personnel
* Max 12 TCFS5089 Fire Display Panel per loop
* Wiring: four bus system
* Display range: any 512 alarm points within nearby 5 loops on its locating loop mainboard
* English comment display
* Dimension: 180mm× 110mm× 40mm
Voltage
Loop : DC24V(16V-28V); Power: DC24V(20V-28V)
Current
Standby Current: loop:≤1.1 mA, Power: < 9mA;
Alarm Current: Loop: ≤2mA, Power:≤45mA
Operating Environment
Temperature: -10°C~+50°C; Relative Humidity:≤9 5%, non-condensing
Wiring
Four-wired
Dimension (LxWxH)
180mmX 110mmx40mm (with base)
Approval
CCCF, CE

TCFSH5206 Water Proof Box For Outdoor Sounder Strobe Fire Alarm 24V
Protection rating: IP67
Material and color of enclosure: ABS
Dimension(L×W×H): 185mm×185mm×75mm
Please shop compatible sounder strobe TC5228
Or confirm the waterproof box is suitable for yours.

TCFSH5231 IP67 Water Proof Box For Module And MCP Fire Security System Wiring
Protection rating: IP67
Material and color of enclosure: ABS
Dimension(L×W×H): 147mm×119mm×79mm
Please buy compatible fire alarm MCP TCSB5264 or confirm the suitable size

TCFSH5203 IP67 Outdoor Sounder Box for TC5231 Fire Alarm Sounder Strobe
Protection rating: IP67
Material and color of enclosure: ABS
Dimension(L×W×H): 147mm×119mm×79mm
Shop below compatible fire sounder strobe

TCDZ517S Sounder base is mainly used in fire alarm systems that require bus-connection. After encoding, it can be used in conjunction with fire alarm smoke detectors and heat detectors. (Compatible with TC5161 and TC5162 and TC5163) When the on-site detection equipment issues an alarm, the sound base can be linked for sound output, prompting the on-site staff to pay attention, so as to better control the on-site situation.
TCDZ 517S Sounder Base characteristic:
1.Two-wire connection with external equipment, convenient on-site wiring;
2.The address is set by electronic coding, no dial switch is needed, and the airtightness is increased in the structure;
3.Use microprocessor to realize signal processing, and use digital signal to communicatewith controller, work stably and reliably, and have a good ability to suppress electromag.
Specification:
Rated working voltage: DC24V
Working current: monitoring current ≤0.18mA starting current ≤5.5mA
Sound pressure level: 65dB ~ 115dB (A weighting)
Coding method: electronic coding method, occupying a bus coding point, the coding range can be set arbitrarily between 1 and 255
Reset method: controller reset
Use environment: Indoor
atmospheric pressure: 86kPa~ 106kPa
Temperature: 0℃~+50℃
Relative humidity ≤95%, non-condensing
Shell material and color: ABS, milky white
Pitch shift periodic: Φ110mm×29mm
Sound type
Sound pressure level: 3.5s~4.5s/0.1s~0.4s