Intelligent Fire Alarm control panel LPCB fire controller 1 Loop 255points (it is also available for 2/3/4 loops).
Color menu display
Intelligent bus control mode; max 255 addressable points
per loop, max 4 loops, max 48 zones
Loop card type design:1-4 loop card can be seledted
Glass fuse per loop
Black box function
Independent controlling password for the specially needed
gas recharging units
Self-design loop protocol
Wall-mounted structure, compact and exquisite
Akzo outer coating;anti-corrosion
Language:English
Approvals:LPCB(EN54-2/4) CE
Core Functions
1. Fire Alarm Monitoring
Detect fire signals from addressable smoke/heat detectors, manual call points, and other fire-sensing devices.
Display the first/last fire alarm, zone location, device address, and time stamp in real time.
Trigger fire alarm output (HJ+/HJ–) and sounder strobe for on-site audible-visual alert.
Fault Detection & Indication
Monitor system faults: main power fault, battery fault, loop communication fault, system fault.
Monitor field device faults: detector fault, module fault, sounder strobe fault, FPE fault, zone fault.
Output fault relay signal and show fault information on LCD and LED indicators.
2. Device & Zone Management
Support up to 4 loops, max 255 addressable points per loop, total 1020 points.
Support up to 48 zones with independent fire alarm and fault/disable indicators.
Support device registration, query, definition (second code, type, attribute, location note).
Support zone/addressable point/sounder/FPE disable and enable.
Linkage Control
Automatically start/stop FPE devices (I/O modules, fire dampers, fire pumps, etc.) via logic linkage formulas.
Support linkage action and feedback signal display.
Support offline programming via USB for linkage logic and device notes.
System Operation & Control
Three-level authority control with password protection (Level I/II/III).
Functions: mute, reset, self-test, silence/resound sounder.
Multi-language switch (Chinese/English) and time/print setup.
Store up to 2000 pieces of fire alarm, fault, and event history logs.
Communication & Networking
Equipped with CAN and RS485 interfaces for CRT connection and networking.
Support master/slave/stand-alone networking mode and information transmission /reception.
Power Management
Dual power supply: AC230V main power + 2×12V12AH backup battery.
Battery charge control, internal resistance detection, and fault alarm.
24V power output for field FPE and sounder strobe.
Display & Output
7-inch color LCD (800×480) for visual information display.
Built-in printer for real-time printing of fire, fault, and event records.
Multi-LED indicator panel for system status, zone status, and FPE status.
3. Installation & Maintenance
Modular plug-in structure for easy installation, commissioning, and expansion.
Loop short-circuit isolation via loop isolator to ensure system stability.
Regular test guidance and common fault troubleshooting.
TECHNICAL SPECIFICATIONS
Volate AC230V(50HZ), Voltage range: +10%--15%
Current 1A
Outputs Fire output .Fault output .24V power output .Loop output
Capacity 1020/4 loops addressable points
LCD screen size 7-inch color LCD screen
Standby bettery 12V/12AH sealed lead acid battery*2
Dimension(L*W*H) 420mm×140mm×560mm
Operating environment Temperature:-5℃-+50℃: Relative Humidity:≤95%non- condensing
Communication interface RS485、CAN、USB
DETAILS
The control panel is mounted on the wall through 4 mounting holes, the dimensions of the mounting holes are shown in the picture.
The right side of the control panel has 8 wiring holes, which are easy for wiring between the control panel and field devices.
There are also 5 knock holes at the top, if the holes on the right side are not enough.
Add compatible detectors and supervisory devices at fire alarm
TCBM5029 addressable fire alarm system programmer for TC-5109 ▪ Contact-type encoding method ▪ Simplify encoding procedure, shorten encoding time, and reduce work intensity ▪ Complete encoding within a second ▪ Greatly improve the efficiency of the engineering commissioning ▪ Manual structure, compact appearance ▪ LCD and English display ▪ Battery management function Technical Specifications Power supply 1.5V/AA battery *2 Operating current ≤40mA Standby current ≤2mA (4mA when the backlight is on) Operating Environment Temperature: -10°C~+50°C,Relative Humidity: ≤95%, non-condensing Dimension (L×W×H):60mm×29mm×155mm Product installation manual and video at fire alarm
$58.00LPCB Approved Intelligent smoke detector Addressable fire alarm system works with TC series addressable fire alarm system LPCB TC-5109 alarm panel fire fighting Infrared scattering principle Non-polarized two-wire Drift compensation and fault detecting function Reporting dirt fault Hotel, restaurant, warehouse, library, office building, teaching building, power plant and other places Approvals:LPCB(EN54-7) CE Technical Specifications Operating voltage Loop 24V(18.5V~26V) Operating current Standby current: ≤0.3mA;Alarm current: ≤0.8mA Operating Environment Temperature: -10°C~+55°C,Relative Humidity: ≤95%, non-condensing Indicator Red,Flashes when polling,Illuminates in alarm Ingress protection rating IP23 Material and color of enclosure ABS; Milky white Coding method Electronically coding Code range 1~255 Weight About 110g Mounting hole distance 60mm Dimension 100mm×51mm (with base) Product installation manual and video at smoke detector
$16.80DC24V LPCB Approved Addressable fire alarm button ressetable manual fire alarm call point works with TC series addressable fire alarm system. Installed in public places; when there is a fire, pressing the frangible element on this MCP can send fire signal to fire alarm control panel Alarm by pressing, reset by a special key Non-polarized two-wire to the control panel Reusable Approvals:LPCB(EN54-7) CE Technical Specifications Operating voltage Loop 24V(18.5V~26V) Operating current Standby current: ≤0.2mA;Alarm current: ≤0.8mA Operating Environment Indoor Temperature: -10°C~+55°C;Relative Humidity: ≤95%, non-condensing Indicator Red. Flashes about every 3s when polling;Illuminates after in alarm Coding method Electronically coding Code range 1~255 Material and color of enclosure ABS; Red Weight About 120g (with base) Mounting hole distance 60mm Dimension (L×W×H) 95mm×44mm×95mm (with base) Product installation manual and video atalarm button
$16.80Addressable fire alarm system LPCB EAC certificate professional fire security equipment. Heat Detector LPCB CE EN54 works with TC-5109 Advanced single-chip microcomputer technology Non-polarized two-wire Indoor garage, kitchen, boiler room, generator room, drying room and other places Approvals:LPCB(EN54-5) CE Technical Specifications Operating voltage Loop 24V(18.5V~26V) Operating current Standby current: ≤0.3mA;Alarm current: ≤0.8mA Operating Environment Temperature: -10°C~+50°C;Relative Humidity: ≤95%, non-condensing Indicator Red,Flashes when polling,Illuminates in alarm Ingress protection rating IP33 Material and color of enclosure ABS; Milky white Coding method Electronically coding Code range 1~255 Weight About 110g Mounting hole distance 60mm Dimension 100mm×50mm (with base) Product installation manual and video at heat detector
$16.80Fire alarm siren works with TC series addressable fire alarm system TC-5109 LPCB alarm panel. LPCB certified addressablel horn strobe flash and sounder Installed in public places A kind of audio and visual alarm device used to warn people in field when fire occurs Four wires:non-polarized signal two-wire, and non-polarized DC24V power two-wire Built-in microprocessor Self-diagnostic function Electronically coding Approvals:LPCB(EN54-3) CE Technical Specifications Operating voltage Loop: 24V (16V~28V);Power: DC24V (DC19V~DC28V) Standby current Loop: ≤0.2mA;Power: ≤0.5mA Active current Loop: ≤1.5mA;Power: ≤50mA Operating Environment Indoor (Non-residential);Temperature: -10°C~+50°C; Relative Humidity: ≤95%(40±2°C) Sound level 80dB~115dB (A weighted) Pitch shift periodic 3.5S~4.5S Basic flashing frequency 1Hz~2Hz Weight 200g Dimension (L×W×H) 115mm×55.3mm×140mm Product installation manual and video can be found at fire horn
$18.50TC5163 Addressable Heat & Smoke Multi Detector:
1. There are 2 conductor pieces with terminals on the base.
Loop of the detector should be connected with two terminals (polarity-insensitive).
After the base is fixed firmly, rotate the bottom of detector and base clockwise, and then the detector will be fitted to the base
2. 1.0mm2 or above RVS twisted pair, laid out through metal conduit or flame-resistant conduit.
TC5163 Smoke and Heat Combined Detector Features:
1. Supervising external circuits function for input and output
2. single chip processes data in real time
3. drift compensation and dust accumulation and report pollution self-diagnosis function
4. non-polarized two wire bus signal fire alarm
TC5163 Smoke and Heat Combined Detector Specification:
Operating Volate: loop 24V(16~28V)
Operating Current: Monitoring current: ≤ 0.3mA ;Alarm current: ≤ 0.9mA
Weight: About 110g
Protected area: 20~30m2
Operating environment: Temperature: -10℃~+55℃; relative humidity: ≤95%, non-condensing
Dimension: 100mm×51mm
Mounting hole distance: 60mm
Ingress protection rating: IP23
Material and color: ABS;Milky white
Maximum transmission range: 1500m

TCMK5265 Addressable I/O Module non-polarized two bus,ultra-low power consumption,no need to add DC24V power supply passive outputvv input and output have isolating loop to effectively filter out external interference 1.Fix the base with two tapping screws,and then connect loop to terminals(polarity-insensitive).After thebase is fixed firmly,rotate the bottom of detector and base clockwise,and then the detector will be fitted tothe base. 2.Wiring instructions:RVS twisted pair with cross-sectional area≥1.0mm2 should be selected for the secondbus of the detector,which should be laid through metal pipe or flame retardant pipe.The length of theconnecting wire should be limited to the single bus resistance≤20Q,otherwise the wire diameter should beincreased. Rated operating voltage Loop:24V(14V~28V); Operating current Monitoring current: ≤ 0.2mA start current: ≤ 0.5mA Operating Environment Temperature:-10℃~+55℃; Relative Humidity:≤95% non-condensing Input supervisory external loop Open circuit occurs when normally open terminal supervising externalloop (short circuit is an action signal), the module will send a fault signalto the control panel. Material and color ABS;Porcelain white Output supervisory external loop Short circuit or open circuit on the output loop occurs, the module will send a fault signal to the contaol panel Weight 147g Mounting hole distance 60mm Dimension(L×W×H) 86mm×38mm×86mm(with base)
$20.00LPCB CERTIFIED TCMK5261 Addressable Single Input Module is used to receive normally open or normally closed swtich signals input by the fire linkage equipment, and transmit linkage information back to the Fire Alarm Control Panel TC5109 (linkage).
Input terminal can be set as normally open and normally closed on-site, which should be connected with passive contact.
The microprocessor monitors the operation situation and transmits the status of the module to the control panel in 3 forms: normal, action and fault.
The circuit part and wiring base are plugged, which is reliable in contact and convenient for construction.
Designed to connect with active devices in field such as water flow indicator, pressure switch, position switch, signal valve and devices able to transmit back switch signals
The built-in microprocessor processes messages intelligently
Plug-in structure
Non-polarized two-wire
Operating voltage: Loop 24V (16V~28V)
Operating current: Standby current:≤0.2mA; Action current:≤0.8mA
Operating Environment
Temperature:-10℃~+55℃; Relative Humidity:≤95% non-condensing
Code range: 1~255
Material and color of enclosure: ABS; Porcelain white
Weight: About 110g(with base)
Mounting hole distance: 60mm
Mounting hole distance: 60mm
Dimension(L×W×H): 86mm×38mm×86mm(with base)
TCMK5269 Dual Input Module is used to receive normally open or normally closed switch signal input by fire linkage equipment, and transmit linkage information back to Fire Alarm controller (linkage type TC5109). It is mainly used to connect various active equipment such as water flow indicator, pressure switch, position switch, signal valve and external linkage equipment which can send back switch signal, etc. After the operation of these devices, the output action signals can be sent by the module to the fire alarm controller through the signal bus to generate an alarm, and the fire alarm controller can be used to linkage the actions of other related devices.
Characteristics
1. The module has two input terminals, respectively input 1 and input 2, respectively corresponding to two addresses;
2. The input line has the function of checking the line, and when the line breaks down, the fault information will be reported;
3. The address code is electronic code, which can be written in advance by the electronic encoder, so the engineering debugging is simple and reliable.
4. Using microprocessor to realize signal processing, using digital signal to communicate with the controller, the work is stable and reliable, and has a good ability to restrain electromagnetic interference
Compatible LPCB Addressable Fire Alarm Systems.

Addressable fire alarm system TC-5109 compatible Single I/O Module LPCB intelligent Module Designed to connect with linkage devices of fire alarm controlpanel, such as exhaust valve, air valve, fire damper etc., and can receive feedback signal from device Non-polarized two-wire Active and passive output The input terminal can be in field set to normally open detecting wire or self-feedback mode, which can be connected with passive contact Approvals:LPCB(EN54-18) CE Technical Specifications Operating voltage Loop:24V (18.5V~26V);Power: DC24V (DC19V~DC28V) Standby current Loop: ≤0.2mA;Power: ≤2mA Starting current Loop: ≤2mA;Power: ≤22mA Operating Environment Temperature: -10°C~+55°C;Relative Humidity: ≤95%, non-condensing Output capacity Passive:Capacity: DC30V/3A;Contact resistance in normal condition: 100kΩ;Closed when activated;Suitable for DC or AC12V~48V;Active output: DC24V/1.5A Indicator Red,Input indicator,Flashes when polling,Illuminates in action,Output indicator,Illuminates in action Coding method Electronically coding Code range 1~255 Material and color of enclosure ABS; Porcelain white Weight About 147g (with base) Mounting hole distance 60mm Dimension (L×W×H) 86mm×38mm×86mm (with base) Product installation manual and video at fire alarm module
$17.90TCSB5214H TC fire alarm system series LPCB approval addressable 2-wire bus type Voltage: Loop DC24V(16V-28V) Digital Manual Call Point (With Jack) (MCP) is installed in public places. The MCP contains a phone jack. And when there is a fire, pressing the frangible element on this MCP can send fire signal to Fire Alarm control panel. After receiving the signal, the control panel will show address information of the MCP and generate alarm sound. Insert the Fire Telephone handle into the phone jack, and then communicate the fire telephone panel. Features 1.Plug-in structure. Simple and convenient installation. Alarm by pressing, reset by a special key. 2.Pressing the frangible element and it can provide independent output contact through the MCP. And it can directly control other peripheral devices. 3.Microprocessor processes signal and digital signal communicates the Fire Alarm Control Panel. Stable and reliable work, good ability to inhibit electromagnetic interference. 4.Electronically addressed. The address can be modified in field. Easy and reliable for commissioning. Technical Specifications 1.Operating voltage Signal bus voltage: loop 24V 2.Operating current Standby current: ≤ 0.2mA Alarm current: ≤ 0.8mA 3.Type of initiating part: Reusable 4.0Initiating mode: Pressing the frangible element manually 5.Resuming mode: Manually resumed by a special key 6.Indicator Running/fire LED: Red. Flashes every 3s when polling. Illuminates after alarming. Fire telephone: Red. Flashes every 5s. 7.Programming mode Electronically addressed (address range: one address within 1~255). 8.Wiring Non-polarized signal two-wire 9.Operating environment Class: indoor Temperature: -10°C~+55°C Relative Humidity: ≤95%, non-condensing 10.Dimension Diameter: 90mm×90mm×42 mm (with base) 11.Material and color of enclosure: ABS; red 12.Weight: about 120g(with base) 13.Mounting hole distance: 60mm 14.Standard: GB 19880-2005 Call Point with Jack
$15.901. Zone Monitoring Interface Description:
TCMK5271 is mainly used to connect external multi-wire conventional detectors to the loop signal bus. It is used to monitor the status of external multi-line equipment and transmit its status to the control panel through the bus. When any detector in the loop sends an alarm signal, the area monitoring interface receives the information and uploads it to the control panel.
2. TCMK 5271 Zone Monitoring Interface Features:
It has the function of detecting the wiring fault of external multi-line equipment;
The address code is electronically coded, which can be written in advance by the electronic encoder, and the engineering debugging is simple and reliable.
Wall-mounted, small size.
3. Specification:
Operating voltage: Rated working voltage of signal bus: bus 24V range: DC16V~DC28V
Power supply rated working voltage: DC24V range: DC20V~DC28V
Operating current:
Bus monitoring current ≤0.25mA
Bus starting current ≤ 0.8ma.
Monitoring current of power supply ≤10mA
and starting current of power supply ≤25mA
Output capacity:
each interface can have up to 30 detectors.
Indicator light:
red, fire alarm light, shining during patrol inspection, and always on. Yellow, fault light, always on.
Coding mode:
electronic coding mode, occupying one bus coding point,
and the coding range can set between 1 and 255.
Wire:
Connect with the signal bus 2-wire of the control panel and the power line
Environment:
Temperature:-10℃ ~+55℃
Relative humidity ≤95%, non-condensing.
Overall dimensions:
86mm×86mm×40mm (with bottom shell)
Material and color:
ABS, porcelain white
Weight:
about 300g
Installation hole distance:
60mm
TCTXM5000-RS MODBUS-RTU CONVERTER is a protocol repeater for fire alarm system monitoring. This product adopts serial communication technology, through accurate data acquisition technology, to monitor, collect and analyze data in an all-round way. Through advanced serial port data transmission technology, the collected data will be sent to the end user. It can monitor the equipment in the fire alarm control panel in real time: alarm, start, stop, feedback, failure, shielding, and supervision and other parameters, the information of the fire alarm control panel can be inquired according to different partitions and addresses. It is easy to install and adopts RS485 serial communication technology to support long-distance wiring. Convenient debugging, configuration parameters can be debugged through the computer serial port, simple, convenient and fast. It is easy to debug and can monitor various parameters of the fire alarm system in real time. When there is information such as fire alarm or fault, the information can be uploaded to the user monitoring system through the serial port query to realize real-time monitoring and real-time processing.
$300.00Addressable Fire Alarm Loop Isolator Module TCMK5210 Wiring type: Non-polar two bus Type: Isolator Action Current: 170mA/270mA Load Capcaity: Loop,24V,170mA/270mA (B, ZX2 short circuit) Mounting Hole Distance: 60mm Ingress Protection Rating: IP30 Specification: 86mm*86mm*40mm (with base) Approval: LPCB, CE, GOST
$18.00TCZS5273 Detector remote indicator light (Hereinafter referred to as remote indicator light)It ismainly used in the bus connection in fire alarm system, It can be used with fire alarm smoke detector,heatdetector and Combination Heat and Smoke Detector.When the installation position of on-site testing equipment is not convenient to ob-serve the alarm state,it can cooperate with the remote indicator light to lead its alarm state to the positioneasy to observe,prompting the field staff to pay attention,so as to better control the scene situation. TCZS 5273 Detector remote indicator features: 1.Two-wire connection with external equipment,convenient on-site wiring 2.Share the address with the matching detection equipment,specifically patrol the indicator light separate-ly,easy to observe the current state of the equipment; 3.Using microprocessor to realize signal processing,using digital signal to communicate with the controller,the work is stable and reliable,and has a good ability to restrain electromagnetic interference TCZS 5273 Detector remote indicator Specification Rated operating voltage DC 24V Working current Monitoring current ≤0.21mA;Starting current ≤0.4mA Operating Environment Class: Indoor atmospheric pressure: 86kPa ~ 106kPa Temperature: 0℃ ~ +50℃ Relative humidity ≤95%, no condensation Indicator green : The fitting equipment shines during inspection Red: the alarm of the matching product is duration bright Electronic encoding method, sharing the same bus coding point with the matching product, the coding range can be set arbitrarily between 1 and 255. Reset mode controller reset Boundary dimension 86mm×86mm Shell material and color ABS, white
$5.50NAJ2214 Addressable Fire Extension Telephone handle works with TCSB5214H or same brand telephone jack It is a bus communication device special for fire protection system. The extension can transmit and receive signals with a Fire Telephone control panel. It is suitable for hotels, restaurants, office buildings, teach buildings, banks, warehouses, libraries, computer rooms and switching rooms. In traditional fire management, some information is managed in the form of paper files. Not only is the data record not comprehensive enough, but also it is difficult to consult and manage because data management is not applied. Tiancheng home safety all-wireless products are combined with the cloud platform, which can fully record and manage all the operation traces of equipment implementation. When the equipment fails, the system will automatically report it to the management party and the maintenance party, and the follow-up inspection and maintenance work will also be recorded in the whole process, so as to change the fire control work mode and further improve the fire control work management efficiency. Frequency Range: 300-3400Hz Operating Current: < 22mA Operating Environment: Temperature: - 10°C~+55°C; Relative Humidity: <95% Function: Matched with NAJ2213&NAJ2215 Dimension: 204 mmx 50mmX 38mm Mounting Hole Distance: 100mm Approval: CCCF
$13.50Product Description
TC-ZJH5008 loop extender is powered by DC24V, and the input and output of bus signals are electrically isolated, which can enhance the anti-interference ability of the whole fire alarm system and has the function of extending the communication distance of the detector bus.
II. Characteristics
1. Built-in isolated power supply with strong interference capability;
2. And the bus and the DC24V power line are non-polar connected;
3. Raise bus voltage and extend bus communication distance;
4. With output short circuit detection function;
5. Up to 255 devices can be attached;
6. Plug-in structure, convenient and reliable installation;
Technical Specifications
1. Operating voltage:
Rated working voltage of signal bus: DC24V range: DC17V~DC28V
Power supply rated working voltage: DC24V range: DC18V~DC36V
2. Operating current:
Monitoring current ≤0.3mA
3. Output capacity: 400mA
4. Load capacity and compatibility: 1 ~ 255 bus devices can be connected, compatible with all detector bus devices.
5. Bus extension distance: 1000m
6. Indicator: There is an answer indicator (red). The indicator does not light when it is normal, and the indicator flashes when the detector answers; With an overload indicator (yellow), the indicator is not on when it is normal, and it is always on when the loop extender output is short-circuited.
7. Environment:
pressure: 86 kPa ~ 106 kPa
Temperature: 0℃ ~+55℃
Relative humidity ≤95%, no condensation.
8. Dimensions: 86mm×86mm×40mm (with cover)
9. Material and color: ABS, porcelain white
10. Weight: about 147g (with cover)
11. Mounting hole distance: 60mm